Wiegand and OSDP reader wiring reference

Conductor counts, common Wiegand color conventions, OSDP RS-485 wiring, cable runs and the differences that matter when you replace a reader.

Always wire from the reader's own installation guide. Colors below are a common convention, used by HID and many others, not a standard. Manufacturers and older readers differ, and a swapped data line produces bad reads rather than an obvious fault.

Wiegand: common conductor colors

ColorFunctionNotes
RedPower, +VUsually 5–16 VDC; check the reader's range.
BlackGroundCommon with the panel's reader ground.
GreenData 0Signals a binary 0.
WhiteData 1Signals a binary 1.
OrangeGreen LED controlPulled low by the panel to show access granted.
BrownRed LED controlPresent on many readers; often unused.
YellowBeeper controlOptional.
DrainShieldGround at the panel end only.

OSDP: four conductors on RS-485

ConductorFunction
Power pair+V and ground
Data pairRS-485 A and B (sometimes marked + and −, or TR+ and TR−), on one twisted pair
DrainShield, grounded at one end

Keep the data on a single twisted pair. Splitting A and B across two pairs, a common shortcut when reusing old Wiegand cable, defeats the noise rejection RS-485 depends on. On long runs, terminate the ends of the bus as the reader and panel manufacturers specify.

The differences that matter

WiegandOSDP
DirectionOne way: reader to panelTwo way: panel and reader talk
Typical maximum runAbout 500 ftAbout 4,000 ft
Readers per cableOneMany, addressed on a shared bus
SupervisionNone. A cut or tapped cable is not reported.The panel polls each reader and reports one that stops answering.
EncryptionNone. Card data crosses the wire in the clear.Secure Channel encrypts traffic with AES-128.
StandardIndustry convention, documented as SIA AC-01SIA OSDP, published internationally as IEC 60839-11-5

When you replace a Wiegand reader with OSDP

  • Confirm the panel or reader interface supports OSDP, and which version, before ordering readers.
  • Existing six- or eight-conductor Wiegand cable will usually work if one twisted pair can carry the data. Test it; old cable is often untwisted or damaged.
  • Set each reader's address and baud rate to match the panel's configuration. Two readers at the same address on one bus will both fail.
  • Turn on Secure Channel and record that it is on. An OSDP reader running without it gives up most of the security benefit.
  • Bench-test one door end to end before you change the rest.

The protocol specification is maintained by the Security Industry Association.