Wiegand and OSDP reader wiring reference
Conductor counts, common Wiegand color conventions, OSDP RS-485 wiring, cable runs and the differences that matter when you replace a reader.
Always wire from the reader's own installation guide. Colors below are a common convention, used by HID and many others, not a standard. Manufacturers and older readers differ, and a swapped data line produces bad reads rather than an obvious fault.
Wiegand: common conductor colors
| Color | Function | Notes |
|---|---|---|
| Red | Power, +V | Usually 5–16 VDC; check the reader's range. |
| Black | Ground | Common with the panel's reader ground. |
| Green | Data 0 | Signals a binary 0. |
| White | Data 1 | Signals a binary 1. |
| Orange | Green LED control | Pulled low by the panel to show access granted. |
| Brown | Red LED control | Present on many readers; often unused. |
| Yellow | Beeper control | Optional. |
| Drain | Shield | Ground at the panel end only. |
OSDP: four conductors on RS-485
| Conductor | Function |
|---|---|
| Power pair | +V and ground |
| Data pair | RS-485 A and B (sometimes marked + and −, or TR+ and TR−), on one twisted pair |
| Drain | Shield, grounded at one end |
Keep the data on a single twisted pair. Splitting A and B across two pairs, a common shortcut when reusing old Wiegand cable, defeats the noise rejection RS-485 depends on. On long runs, terminate the ends of the bus as the reader and panel manufacturers specify.
The differences that matter
| Wiegand | OSDP | |
|---|---|---|
| Direction | One way: reader to panel | Two way: panel and reader talk |
| Typical maximum run | About 500 ft | About 4,000 ft |
| Readers per cable | One | Many, addressed on a shared bus |
| Supervision | None. A cut or tapped cable is not reported. | The panel polls each reader and reports one that stops answering. |
| Encryption | None. Card data crosses the wire in the clear. | Secure Channel encrypts traffic with AES-128. |
| Standard | Industry convention, documented as SIA AC-01 | SIA OSDP, published internationally as IEC 60839-11-5 |
When you replace a Wiegand reader with OSDP
- Confirm the panel or reader interface supports OSDP, and which version, before ordering readers.
- Existing six- or eight-conductor Wiegand cable will usually work if one twisted pair can carry the data. Test it; old cable is often untwisted or damaged.
- Set each reader's address and baud rate to match the panel's configuration. Two readers at the same address on one bus will both fail.
- Turn on Secure Channel and record that it is on. An OSDP reader running without it gives up most of the security benefit.
- Bench-test one door end to end before you change the rest.
The protocol specification is maintained by the Security Industry Association.