Low-voltage wire resistance and voltage drop by gauge

DC resistance of 8 to 22 AWG copper and twisted-pair cable, with the voltage lost per 100 feet of run at common lock and reader currents.

Voltage lost per 100 feet of run

Solid copper at 20 °C. A run of 100 feet is 200 feet of conductor, out and back, and that is what the table counts.

GaugeΩ per 1,000 ftAt 250 mAAt 500 mAAt 1 AAt 2 A
22 AWG16.1400.81 V1.61 V3.23 V6.46 V
20 AWG10.1500.51 V1.02 V2.03 V4.06 V
18 AWG6.3850.32 V0.64 V1.28 V2.55 V
16 AWG4.0160.20 V0.40 V0.80 V1.61 V
14 AWG2.5250.13 V0.25 V0.51 V1.01 V
12 AWG1.5880.08 V0.16 V0.32 V0.64 V
10 AWG0.9990.05 V0.10 V0.20 V0.40 V
8 AWG0.6280.03 V0.06 V0.13 V0.25 V

To use it: multiply the figure by the run length in hundreds of feet, and subtract from the supply voltage. A 12 VDC magnetic lock drawing 500 mA at the end of 250 feet of 18 AWG loses about 0.64 V × 2.5 = 1.6 V, and sees roughly 10.4 V.

Twisted-pair cable, per conductor

CableΩ per meterΩ per 100 ft
Cat5e — 24 AWG solid0.08422.57
Cat6 — 23 AWG solid0.06682.04
Cat6A — 23 AWG solid0.06682.04
Cat6 — 24 AWG solid0.08422.57
CCA 24 AWG (not standards compliant)0.14004.27

Rules of thumb that hold up

  • Check the voltage at the device against its minimum operating voltage, not against an arbitrary percentage.
  • Recheck at the battery's end-of-discharge voltage. A 12 V system on battery may start near 10.5 V before any drop at all.
  • Going to 24 VDC halves the current for the same power and cuts the drop to a quarter in percentage terms. Use it for long lock runs where the hardware allows.