Voltage Drop

What voltage actually arrives at the device on a 12 or 24 VDC run, checked against its minimum operating voltage.

Planning estimates only. This calculator is not a substitute for engineered design or manufacturer specifications. Verify the final design against OEM documentation and the codes your authority having jurisdiction enforces.

The formula

Exactly what the calculator computes, in the order it computes it. Highlighted terms are your inputs.

// Both conductors carry the current, so the length doubles
loopResistance = 2 × (runLength(ft) ÷ 1000) × ohmsPer1000ft

voltageDrop    = current × loopResistance          Ohm's law
voltageAtDevice = supplyVoltage − voltageDrop
percentDrop     = voltageDrop ÷ supplyVoltage

// Longest run before the device minimum is reached
maxLength = (supplyVoltage − deviceMinimum) × 1000
            ─────────────────────────────────────────────
                    2 × current × ohmsPer1000ft

PASS when voltageAtDevice ≥ deviceMinimum

What it assumes

Each of these is a way the number can be wrong for your job. Read them before you buy hardware.

  1. DC only. This is a pure resistance calculation for DC circuits. It does not apply to AC runs, where inductive reactance and power factor matter.
  2. Solid uncoated copper at 20 °C. Resistance values follow the standard AWG table. Copper resistance rises roughly 0.4% per °C — a run through a 50 °C plenum carries about 12% more drop than calculated. Stranded conductor is marginally higher again.
  3. Enter the measured supply voltage, not the nominal rating. This is the most common source of error. A "12 V" power supply typically floats at 13.6–13.8 V, and a "24 V" supply at 27.2–27.6 V. But on battery standby that same supply falls toward 10.5 V as the battery discharges — and that is exactly when the device still has to work. Run the calculation twice: once at float, once at end-of-discharge.
  4. Steady-state current only. Inrush is not modelled. Electric strikes, maglocks, sirens, and motorised devices draw substantially more on energisation, and the momentary drop is larger than shown. Use the worst-case continuous draw and treat the result as optimistic for inrush.
  5. One device at the end of the run. For multiple devices tapped along a run, the drop is not uniform — calculate segment by segment, or as a worst case put the whole load at the far end.
  6. Perfect terminations assumed. No allowance for splices, terminal resistance, corrosion, or a poorly seated connector. In the field these are a frequent cause of drop beyond calculation, particularly in exterior and below-grade work.
  7. Aim for margin, not a bare pass. A result that clears the minimum by a tenth of a volt is a callback waiting to happen. Common practice targets no more than 10% drop, and leaving a volt in hand costs very little at installation.

Questions people ask

How far can I run 18 AWG for a 12 V maglock?
It depends on the lock current and its minimum operating voltage. At 500 mA, 18 AWG loses about 0.64 V per 100 feet of run, out and back, so a few hundred feet can drop a 12 V lock below its rating.