Lock Power Budget
Power supply size for an access control door set: locks, readers and sensors, the worst-case simultaneous unlock, and the battery standby that follows.
Planning estimates only. This calculator is not a substitute for engineered design or manufacturer specifications. Verify the final design against OEM documentation and the codes your authority having jurisdiction enforces.
The formula
Exactly what the calculator computes, in the order it computes it. Highlighted terms are your inputs.
// Sum each device's current by how it draws continuous = Σ qty × mA where it draws continuously energized = Σ qty × mA where it draws only when unlocked // Worst case: everything continuous, plus the share of locks unlocked together peak = continuous + energized × simultaneous% supply = peak × (1 + headroom) // Standby, as in the Battery Standby calculator battery Ah = continuous × standbyHours × 1.25
What it assumes
Each of these is a way the number can be wrong for your job. Read them before you buy hardware.
- Enter datasheet currents, not the defaults. The starting rows are plausible examples, not values for any specific product. Lock current varies widely by model, holding force and voltage.
- Fail-safe locks draw while locked; fail-secure locks draw while unlocked. A magnetic lock holds the door with current and releases when power is removed. A fail-secure strike is the reverse. Set each row accordingly.
- Inrush is not modelled. Solenoid strikes and some motorized locks pull a short surge well above their holding current when they operate. The headroom covers ordinary inrush; check the supply manufacturer's guidance for motorized hardware.
- Battery charging uses supply capacity. Many supplies divide their rating between the load and the battery charger. Check whether the datasheet rating is before or after charging current.
- Voltage drop is separate. A supply with enough current can still deliver too few volts to the far door. Check long runs with the Voltage Drop calculator, especially at 12 VDC.
- Life safety governs. Fail-safe locking on egress doors, fire alarm release and delayed egress are governed by NFPA 101, the IBC and the authority having jurisdiction. This calculator sizes power; it does not decide which hardware is permitted on a door.
Questions people ask
- How big a power supply do I need for magnetic locks?
- Add the holding current of every fail-safe lock, since they draw whenever they are locked, plus readers and sensors, then add about 25% headroom. Fail-secure strikes add their current only when energized, so plan for the moment a fire alarm release or schedule unlocks every door at once.
More power and cabling tools
- PoE Budget Total switch power required by a device list, with cable loss and headroom against the switch you actually specified.
- Voltage Drop What voltage actually arrives at the device on a 12 or 24 VDC run, checked against its minimum operating voltage.
- Battery Standby Amp-hour capacity required to hold a system up for the standby period, with derating for age and temperature.
- Conduit Fill Fill percentage for a conductor list against the NEC limits, with the smallest trade size that passes.