Conduit Fill
Fill percentage for a conductor list against the NEC limits, with the smallest trade size that passes.
Planning estimates only. This calculator is not a substitute for engineered design or manufacturer specifications. Verify the final design against OEM documentation and the codes your authority having jurisdiction enforces.
The formula
Exactly what the calculator computes, in the order it computes it. Highlighted terms are your inputs.
// Cross-sectional area of each round cable cableArea = π × (outsideDiameter ÷ 2)² totalArea = Σ ( quantity × cableArea ) // Fill against the conduit internal area (NEC Chapter 9, Table 4) fill% = totalArea ÷ conduitInternalArea × 100 // Permitted fill (NEC Chapter 9, Table 1) 1 conductor → 53% 2 conductors → 31% 3 or more → 40% PASS when fill% ≤ limit // Spare capacity for additional cable spareArea = (conduitInternalArea × limit) − totalArea
What it assumes
Each of these is a way the number can be wrong for your job. Read them before you buy hardware.
- NEC Chapter 9 areas and limits. Internal areas follow Table 4 and the fill percentages follow Table 1. These tables are revised between editions — verify against the NEC edition your AHJ has adopted, and note that some jurisdictions amend them.
- The two-conductor 31% limit is easy to miss. It is lower than both the single-conductor and the three-or-more limit. It exists because two round cables pack poorly, not as an arbitrary rule.
- Round cables assumed. Area is calculated from a circular cross-section. Flat, oval, or irregular cable will not pack as the arithmetic suggests — use the manufacturer's stated cross-sectional area for anything non-round.
- Published cable ODs are nominal. Real diameters vary by manufacturer, jacket rating, and production lot. Plenum-rated cable is often a different diameter from riser-rated cable of the same type. Measure the cable you are actually pulling for anything close to the limit.
- Fill is not the only limit. A run that passes fill can still be unpullable. Bend count and radius, run length, pull tension, jam ratio, and lubrication all matter. NEC limits total bends to 360° between pull points, and long runs with multiple bends need derating well below the fill limit.
- Jam ratio is not checked. Three cables of similar diameter in a conduit whose inner diameter is 2.8–3.2 times the cable OD can jam regardless of fill percentage. This is a common failure on three-cable pulls.
- Nipples are exempt. Conduit nipples 24 inches or shorter between boxes are permitted 60% fill under NEC Chapter 9 Note 4. This calculator does not apply that exception.
- Derating and separation are separate questions. Fill says nothing about ampacity derating for current-carrying conductors, nor about required separation between power and communications cabling. Both may govern before fill does.
- Design below the limit. Filling to exactly 40% leaves nothing for the moves, adds, and changes that always come. Common practice targets 25–30% on new work so the next technician has somewhere to put a cable.
Questions people ask
- How many Cat6 cables fit in 3/4 inch EMT?
- At the NEC 40% limit for three or more cables, about four Cat6 UTP cables of 0.24 inch diameter. Most designers target 25 to 30% fill on new work so the conduit can take another cable later.
More power and cabling tools
- PoE Budget Total switch power required by a device list, with cable loss and headroom against the switch you actually specified.
- Lock Power Budget Power supply size for an access control door set: locks, readers and sensors, the worst-case simultaneous unlock, and the battery standby that follows.
- Voltage Drop What voltage actually arrives at the device on a 12 or 24 VDC run, checked against its minimum operating voltage.
- Battery Standby Amp-hour capacity required to hold a system up for the standby period, with derating for age and temperature.
Need it designed, installed or maintained?
We design and maintain these systems for federal facilities. Bring us the drawings.